TESTING OF FIRE ALARM SYSTEMS

Have your information together BEFORE you TEST:

Completion Documents, 72-13, 7.5

Record of Completion, 72-13, 7.8.2(a)

Owner's Manual and Manufacturer's published instructions for ALL equipment, 72-13,7.5.3(1)

​Record Copy of site-specific Software, 72-13, 7.5.7

INDUSTRY NEWS ABOUT FIRE ALARMS 

AVERAGE AMBIENT SOUND LEVEL

The 2016 edition of NFPA 72 National Fire Alarm and Signaling Code states the AVERAGE AMBIENT SOUND LEVEL is the root mean square, A-weighted, sound pressure level measurement over a period of time that any person is present, or a 24-hour period, whichever time period is the lesser.

TX Fire Lady

DOCUMENT BOX

The 2013 edition of NFPA 72 National Fire Alarm and Signaling Code now states that every new fire alarm system shall have a Document box or cabinet.  It can be located next to the fire alarm control panel or in a different location that is identified at the fire alarm control. 7.7.2.


PHOTOELECTRIC SMOKE DETECTORS

The 2016 edition of NFPA 72 National Fire Alarm and Signaling Code states that photoelectric smoke detectors use either Light Obscuration or Light Scattering technology.



NEW REQUIREMENTS FROM BEXAR COUNTY


All testing and inspection reports are to be send to the web-based  ComplianceCenter. If your customers buildings have any of the fire protection systems listed, the test and inspection reports for these systems are now required to be filed electronically.

  • Fire Alarm
  • Fire Sprinkler
  • Kitchen range hood cleaning
  • Kitchen range hood suppression
  • Fire Extinguisher


Go to www.Bexar.org/fm